The burner control box DMG 972-N controls and supervisespower burner for gas and dual fuel. The control box isapproved and certified according the relevant Europeanstandards. The use on direct air heaters according DIN 4794is also possible. With the facility to connect an air damper unit, a 2 stage operation with two fuel valves or a modulating operation with one fuel valve is possible.
Specifications:
- Complete reference: DMG 972-N mod. 01 (0452001U Honeywell), DMG 972-N mod. 04 (0452004U Honeywell)
- For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit.
A Honeywell Company certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr.12-00-e/01/99 INTRODUCTION The burner control box DMG 972 controls and supervises power burner for gas and dual fuel. The control box is approved and certified according the relevant European standards. The use on direct air heaters according DIN 4794 is also possible. Control Box DMG 972 Mod.01. Operating voltage. 220 / 240 V (-15. +10%) 50 Hz ( ±5%) Contorl Box DMG972-N Mod.01 unit pack. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit. Possible flame detectors: - Ionisation probe - Infrared flicker detector 1020 - UV flame sensor UVD 971. Shipping Weight: 1.5 kg.
- Flame detection: ionisation probe, infrared-flicker detector IRD 1020, UV flame sensor UVD 971Model | Max. Reaction time for airproving switch tlw | Supervised pre-purge time tv1 | Pre-ignition time tvz | Stray light monitoring tf | Safety time ts | Post-ignition time tn | Delay 2nd-stage tv2 | Power supply |
01 (0452001U) | 60 | 54 | 3 | 5 | 3 | 2 | 8 | 220-240 V |
04 (0452004U) | 42 | 3 | 5 | 2 | 1.5 | 10 |
Model selection guide and technical data sheet (pdf)
The burner control box DKG 972-N Satronic controls and supervises atmospheric burners for gas. They are approved and certified according to the applicable European standards and regulations. The microprocessor-based programming sequence ensures extremely stable timings independent of voltage variations, ambient temperature and/or switch-on cycles.- Complete reference: DKG 972-N mod. 05 (0432005U Honeywell), DKG 972-N mod.10 (0432010U Honeywell), DKG 972-N mod. 20 (0432020U Honeywell)
- Flame detection: ionisation probe, infrared-flicker detector IRD 1020, UV flame sensor UVD 971Model | Waiting time start tw | Pre-ignition time tvz | Stray light monitoring tf | Safety time ts | Post-ignition time tn | Delay 2nd-stage tv2 | Power supply |
05 (0432005U) | 12 | 3 | 5 | 5 | 3.8 | 25 | 220 - 240 V |
10 (0432010U) | 10 | 8.8 | |||||
20 (0432020U) | 20 | 18.8 |
Model selection guide and technical data sheet (PDF)
THIS MODEL REPLACES THE OBSOLET DKG972